The Study of Performance Comparison of Flat Plate and Evacuated Tube Collectors for Domestic Hot Water Heating Systems in Kerman
Author/Authors :
Hadi Farzan Mechanical Engineering Department - Higher Educational Complex of Bam, 76615-314, Bam, Iran
كليدواژه :
Plat plate collector , Evacuated tube collector , Energy performance analysis , Economic analysis , Solar water heater , Solar fraction
عنوان كنفرانس :
ششمين كنفرانس ملي ساليانه انرژي پاك
چكيده لاتين :
This study represents a year round energy performance of two solar water heater
(SWH) systems with 4m2 flat plate collector (FPC) and evacuated tube collector
(ETC) operating under the same weather conditions. The energy performance of the
two considered systems was compared on monthly and yearly basis. The obtained
results showed that for an annual total solar insolation of 2 2056kWhm , the total of
1 3577kWhy and 1 4201kWhy heat energy were collected by 4m2 FPC and ETC
systems, respectively. The annual average efficiency by FPC system was 43%, while
its annual solar fraction was 50%. The ETC system had 51% efficiency with 58%
solar fraction. The economic analysis showed that both solar water heating system
are not economically viable under prevailing costs in Iran. Furthermore, according
to the obtained results the FPCs are more favorable than the ETCs due to its
economic analysis and energy performance. These results provide useful information
for households and policy makers.