  • Abstract
    A precision current transformer for the audio-frequency band in which an auxiliary current transformer equalizes the potential along the primary and secondary windings of the main current transformer is discussed. The arrangement results in a dramatic reduction of capacitive leakage current. In this way, a ratio error of less than 10 p.p.m. and phase angle error of less than 10 μrad is achieved at frequencies up to 10000 Hz
  • Keywords
    current transformers; leakage currents; measurement errors; measurement standards; power measurement; 10000 Hz; audio-frequency power standard; capacitive leakage current; current transformer; phase angle error; precision transformer; primary windings; secondary windings; Capacitance; Current transformers; Frequency conversion; Impedance; Leakage current; Magnetic cores; Metrology; Standards development; Thermal stability; Voltage;