    Study on reduction in electric field, charged voltage, ion current and ion density under HVDC transmission lines by parallel shield wires

  • Author

    Amano, Yuji ; Sunaga, Yoshitaka

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
  • Volume
    4
  • Issue
    2
  • fYear
    1989
  • fDate
    4/1/1989 12:00:00 AM
  • Firstpage
    1351
  • Lastpage
    1359
  • Abstract
    Several models of shield wire were tested with the Shiobara HVDC (high-voltage direct current) test line. The models contain typical standard wires that are generally used to reduce field effects at ground level, neutral conductors placed at lower parts of the DC line, and an earth corona model to intentionally cancel positive or negative ions by generating ions having opposite polarity to ions flowing into the wire. The authors describe experimental results on the effects of these shield wires and a method to predict shielding effects. It is concluded that shielding using the earth corona is quite an effective method; it is even applicable to the reduction of ion density, which has normally been considered difficult
  • Keywords
    corona; electric fields; ion density; power overhead lines; shielding; HVDC transmission lines; charged voltage reduction; earth corona model; electric field reduction; ion current reduction; ion density reduction; neutral conductors; parallel shield wires; Circuit testing; Conductors; Corona; Current density; Electric shock; Electric variables measurement; HVDC transmission; Power transmission lines; Voltage; Wires;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.25622
  • Filename
    25622