Abstract
Several models of shield wire were tested with the Shiobara HVDC (high-voltage direct current) test line. The models contain typical standard wires that are generally used to reduce field effects at ground level, neutral conductors placed at lower parts of the DC line, and an earth corona model to intentionally cancel positive or negative ions by generating ions having opposite polarity to ions flowing into the wire. The authors describe experimental results on the effects of these shield wires and a method to predict shielding effects. It is concluded that shielding using the earth corona is quite an effective method; it is even applicable to the reduction of ion density, which has normally been considered difficult
Keywords
corona; electric fields; ion density; power overhead lines; shielding; HVDC transmission lines; charged voltage reduction; earth corona model; electric field reduction; ion current reduction; ion density reduction; neutral conductors; parallel shield wires; Circuit testing; Conductors; Corona; Current density; Electric shock; Electric variables measurement; HVDC transmission; Power transmission lines; Voltage; Wires;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.25622
Filename
25622
Link To Document