• DocumentCode
    1017439
  • Title

    DC contamination performance of station insulators

  • Author

    Naito, K. ; Kunieda, S. ; Hasegawa, Y. ; Ito, S.

  • Volume
    23
  • Issue
    6
  • fYear
    1988
  • Firstpage
    1015
  • Lastpage
    1023
  • Abstract
    The authors describe the results of an investigation of the contamination performance of equipment insulators under the application of a DC voltage. Artificial contamination tests on insulators with various shed profiles were carried out. In addition to total leakage distance, shed profile is found to play a role in determining the DC withstand voltage. Deep-rib-type insulators exhibit a superior DC contamination performance compared to other types of insulators. Anticontamination design criteria that are based on the results of the investigation are given for DC equipment insulators.<>
  • Keywords
    insulators; DC equipment insulators; DC voltage; DC withstand voltage; contamination performance; shed profiles; station insulators; total leakage distance; Accidents; Contamination; Flashover; HVDC transmission; Insulation; Insulator testing; Large-scale systems; Surges; Transmission lines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/14.16528
  • Filename
    16528