• DocumentCode
    1024081
  • Title

    Impact of inverter station on torsional dynamics of parallel HVDC-AC power system

  • Author

    Iravani, M.R. ; Zhao, Z. ; Hamouda, R.M.

  • Author_Institution
    Dept. of Electr. Eng., Toronto Univ., Ont., Canada
  • Volume
    8
  • Issue
    3
  • fYear
    1993
  • fDate
    8/1/1993 12:00:00 AM
  • Firstpage
    997
  • Lastpage
    1003
  • Abstract
    The authors investigate the impact of an inverter station on the torsional dynamics of a turbine-generator set which is located at the rectifier side of a parallel HVDC-AC power system. The stiffness of an AC bus is described in terms of its effective short-circuit ratio (ESCR). The studies show that depending on the stiffness of the inverter AC bus and electrical coupling between the inverter and rectifier AC buses, the inverter closed loop control can have a noticeable contribution to the instability of torsional dynamics. This adverse torsional impact is observed in the study results even when the inverter AC bus is fairly strong (ESCR larger than 5.0)
  • Keywords
    closed loop systems; invertors; power system interconnection; short-circuit currents; substations; torsion; AC bus; effective short-circuit ratio; electrical coupling; inverter closed loop control; inverter station; parallel HVDC-AC power system; rectifier side; torsional dynamics; turbine-generator set; AC generators; Control systems; Couplings; Frequency; HVDC transmission; Inverters; Power system dynamics; Power system harmonics; Rectifiers; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/59.260901
  • Filename
    260901