DocumentCode :
1027718
Title :
Field Measurement of 345-Kv Lightning Arrester Switching Surge Perrormance
Author :
Price, W.S. ; McElroy, A.J. ; Smith, H.M. ; Shankle, D.F.
Author_Institution :
American Electric Power Service Corporation
Volume :
82
Issue :
67
fYear :
1963
Firstpage :
487
Lastpage :
500
Abstract :
The purpose of this paper is to present lightning arrester switching surge voltages and currents, measured during a field test program on a 345-kv system. Surges were produced by energization of a transformer-terminated line and by ultra-high-speed re-energization (UHSR) of arrester-terminated lines. Arrester-sparkover levels were 1.1 to 1.7 pu (per unit) of arrester rating, and arrester follow-current peaks were 135 to 940 amperes.
Keywords :
Analog computers; Arresters; Continuous improvement; Costs; Current measurement; Lightning; Power transformer insulation; Shape; Surge protection; System testing;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1963.291442
Filename :
4072824