DocumentCode
1027896
Title
Pre-screening of single contingencies causing network topology changes
Author
Brandwajn, V. ; Liu, Y. ; Lauby, M.G.
Author_Institution
ABB Power Autom., Palo Alto, CA, USA
Volume
6
Issue
1
fYear
1991
fDate
2/1/1991 12:00:00 AM
Firstpage
30
Lastpage
36
Abstract
A multilevel contingency screening method is introduced to process large sets of candidate power system contingencies. The idea is to apply a series of increasingly more accurate and time-consuming algorithms so that each higher screening level processes a reduced set of candidates. A practical implementation of the method uses a fast prescreening step whose algorithm is based upon the local network solution concept. The method is designed to process contingencies whose effects can be localized, e.g. branch outages and bus section faults. The accuracy of the new algorithm is controlled via an automatically calculated small network adequacy ratio while its reliability is enhanced by the use of different contingency severity measures
Keywords
electrical faults; power system analysis computing; reliability; algorithms; branch outages; bus section faults; fast prescreening step; local network solution concept; multilevel contingency screening method; network topology; power system analysis computing; reliability; Automatic control; Automation; Control systems; Design methodology; Energy management; Medical services; Network topology; Process design; Senior members; Stress measurement;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.131044
Filename
131044
Link To Document