• DocumentCode
    1028526
  • Title

    Interim Report-Minimum Electrical Clearances ror Substations Based on Switching Surge Requirements

  • Author

    Report, AIEE

  • Volume
    82
  • Issue
    69
  • fYear
    1963
  • Firstpage
    1072
  • Lastpage
    1076
  • Abstract
    A method has been developed for estimating line-to-ground and phase-to-phase clearances to withstand switching surge voltages in substations. Clearances have been calculated for standard system operating voltages through 500 kv with an assumed switching surge magnitude of 2.8 times the maximum line-to-neutral crest voltage. Consideration has been given to the simultaneous occurrence of opposite polarity switching surges on adjacent phases. Clearance values will be verified by testing programs before being recommended for design purposes.
  • Keywords
    Electrodes; Flashover; Frequency; Safety; Standardization; Substations; Surges; Transient analysis; Voltage control; World Wide Web;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1963.291495
  • Filename
    4072909