• DocumentCode
    1032079
  • Title

    A New High Pass Coupling Network for Power Line Carrier Operation - Field Test Report

  • Author

    Brown, Ronald W. ; Kopischke, Gerald L.

  • Author_Institution
    Interstate Power Company
  • Issue
    5
  • fYear
    1967
  • fDate
    5/1/1967 12:00:00 AM
  • Firstpage
    563
  • Lastpage
    567
  • Abstract
    Field tests of a new high pass coupling network for power line carrier operation are discussed. The tests pointed out several weaknesses in the coupling system as originally designed and installed. Redesign of coupling units and installation of auxiliary capacitors on the substation bus improved the attenuation characteristics and low-frequency cut-off point of the networks, resulting in satisfactory operation. Results of field test measurements are shown for the original and for the modified systems.
  • Keywords
    Capacitors; Couplings; Frequency shift keying; Inductors; Power system relaying; Power transmission lines; Radio frequency; Solid state circuits; Substations; System testing;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1967.291732
  • Filename
    4073317