Bus Transfer Tests on 2,300-Volt Station Auxiliary System
Author
Johnson, A.A. ; Thompson, H.A.
Author_Institution
Westinghouse Electric Corporation, East Pittsburgh, Pa.
Volume
69
Issue
1
fYear
1950
Firstpage
386
Lastpage
394
Abstract
Transfer tests were made of one auxiliary bus section in a large power station from one source to another source. The two sources, one an auxiliary generator and the other a service transformer, were not paralleled during the transfer operation. The optimum open time interval was determined and inrush currents, voltage changes, and some power measurements were made on the combined bus load and on several individual motors. Successful transfers were made at time intervals up to about 150 cycles. The motors, the auxiliary generator, and the station boilers operated satisfactorily for all tests.
Keywords
Circuit breakers; Circuit testing; Induction generators; Induction motors; Power generation; Power system protection; Power system relaying; Power system reliability; System testing; Voltage;