• DocumentCode
    1036493
  • Title

    Bus Transfer Tests on 2,300-Volt Station Auxiliary System

  • Author

    Johnson, A.A. ; Thompson, H.A.

  • Author_Institution
    Westinghouse Electric Corporation, East Pittsburgh, Pa.
  • Volume
    69
  • Issue
    1
  • fYear
    1950
  • Firstpage
    386
  • Lastpage
    394
  • Abstract
    Transfer tests were made of one auxiliary bus section in a large power station from one source to another source. The two sources, one an auxiliary generator and the other a service transformer, were not paralleled during the transfer operation. The optimum open time interval was determined and inrush currents, voltage changes, and some power measurements were made on the combined bus load and on several individual motors. Successful transfers were made at time intervals up to about 150 cycles. The motors, the auxiliary generator, and the station boilers operated satisfactorily for all tests.
  • Keywords
    Circuit breakers; Circuit testing; Induction generators; Induction motors; Power generation; Power system protection; Power system relaying; Power system reliability; System testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1950.5060162
  • Filename
    5060162