Title
Fair-Weather RI, Part I: Artificial and Natural Sources
Author
Liao, Tseng-Wu ; Hoglund, Norman A.
Author_Institution
General Electric Company
Issue
5
fYear
1970
fDate
5/1/1970 12:00:00 AM
Firstpage
837
Lastpage
844
Abstract
Based on the present state of the art a simplified picture depicting the characteristic of corona plumes and RI generation from EHV line conductors during fair weather is presented. An artificial source was developed to simulate some natural sources that were identified in the field insofar as plume and RI generation are concerned. By means of the artificial source, a prediction is made on the RI levels expected from UHV transmission lines. The prediction is based on laboratory test results from the artificial sources on conductors of different diameters but presumes the same number of sources per mile of UHV line as for EHV lines. Further investigations are required to verify this assumption.
Keywords
Conducting materials; Conductors; Corona; Economic forecasting; Laboratories; Noise level; Power generation economics; Power transmission lines; Surface cleaning; Surface contamination;