DocumentCode
1039933
Title
Damping of Power Oscillations in Salient-Pole Machines with Static Exciters
Author
Byerly, Richard T. ; Keay, F.W. ; Skooglund, John W.
Author_Institution
Westinghouse Electric Corporation
Issue
6
fYear
1970
fDate
7/1/1970 12:00:00 AM
Firstpage
1009
Lastpage
1021
Abstract
It is generally accepted that a high-performance excitation system may reduce the effective internal damping of a synchronous machine. Alternately, studies and field tests indicate that a fast-acting excitation system offers the best opportunity for increased damping through the use of an auxiliary signal into the voltage regulator. The application of static exciters to water-wheel generators requires an awareness of these possible changes in machine damping. The use of an auxiliary damping signal into the voltage regulator may become especially important for machines that are inherently lightly damped.
Keywords
Bars; Character generation; Damping; Iron; Power generation; Regulators; Rotors; Shock absorbers; Synchronous machines; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1970.292688
Filename
4074163
Link To Document