DocumentCode :
1041639
Title :
Detection of Slot Discharges in High-Voltage Stator Windings During Operation
Author :
Johnson, John S. ; Warre, Mead
Author_Institution :
Westinghouse Electric Corporation, East Pittsburgh, Pa.
Volume :
70
Issue :
2
fYear :
1951
fDate :
7/1/1951 12:00:00 AM
Firstpage :
1998
Lastpage :
2000
Abstract :
A modified slot discharge detection method, which permits tests without Shutting down the machine or using auxilliary high-voltage test equipment, was investigated. The method involves connection of frequency sensitive equipment across all or part of the ntral impedance. Tests on eight vertical water wheel generators in the range of 20,000- to 40,000-kva capacity indicate that the method is generally applicable when there is a current transformer or some other impedance in the generator neutral.
Keywords :
Bars; Coils; Current transformers; Frequency; Insulation; Power harmonic filters; Stator windings; Surface discharges; Surface impedance; Testing;
fLanguage :
English
Journal_Title :
American Institute of Electrical Engineers, Transactions of the
Publisher :
ieee
ISSN :
0096-3860
Type :
jour
DOI :
10.1109/T-AIEE.1951.5060664
Filename :
5060664
Link To Document :
بازگشت