DocumentCode :
1042386
Title :
New method for derating cables in trays traversing firestops
Author :
Save, Phil ; Engmann, Gary
Author_Institution :
Southern California Edison, Co., Los Angeles, CA, USA
Volume :
3
Issue :
2
fYear :
1988
fDate :
6/1/1988 12:00:00 AM
Firstpage :
217
Lastpage :
224
Abstract :
An attempt is made to show that the Namgne method (R. Namgne and L. Ashbaugh, 1977) is simple and practical bt clarifying the analytic evaluation, and presenting a simpler step-by-step method for calculation of allowable ampacity. Using this method, a computer program has been developed to generate tables of correction factors which can be directly applied to the ICEA P-54-440 ampacities. Experimental results and the theoretical basis of method presented in references, are reviewed, and a comparison is made of the Namgne method with other approaches
Keywords :
electrical engineering computing; power cables; ICEA P-54-440 ampacities; Namgne method; allowable ampacity calculation; cable derating; computer program; correction factors; firestops; Cables; Conducting materials; Cooling; Heat transfer; Power generation; Region 1; Region 2; Solid modeling; Temperature; Thermal conductivity;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/60.4721
Filename :
4721
Link To Document :
بازگشت