Title :
An Investigation on the Nondetection Zones of Synchronous Distributed Generation Anti-Islanding Protection
Author :
Vieira, Jose C M ; Freitas, Walmir ; Xu, Wilsun ; Morelato, Andre
Author_Institution :
USP, Sao Carlos
fDate :
4/1/2008 12:00:00 AM
Abstract :
Anti-islanding protection is an important technical requirement when interconnecting distributed generators. Unfortunately, most anti-islanding protection schemes cannot detect islanding situations under certain system operating conditions - there are nondetection zones within which anti-islanding protection schemes are ineffective. This paper investigates these nondetection zones associated with the common anti-islanding protection schemes of synchronous distributed generators: frequency and voltage-based relays. Moreover, the characteristics of the nondetection zones and the key factors that influence them are analyzed. The results are useful for utility companies and distributed generators owners to design and to evaluate the effectiveness of anti-islanding protection schemes proposed for various distributed generation interconnection projects.
Keywords :
distribution networks; power generation protection; relay protection; synchronous machines; anti-islanding protection; frequency-based relays; nondetection zones; synchronous distributed generation; synchronous distributed generators; synchronous machines; voltage-based relays; Distributed generation (DG); frequency relay; islanding; nondetection zones; synchronous machines; voltage relay;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2007.915831