Title :
Measurements of contamination on post insulators in HVDC converter stations
Author_Institution :
General Electric Co., Lenox, MA, USA
fDate :
1/1/1988 12:00:00 AM
Abstract :
The severity of the effects of contamination on post insulators in four different HVDC converter stations is illustrated by a series of field measurements. The data are analyzed to show the effects of polarity, stress, voltage magnitude, and distribution of contaminant along and around the insulators. Recommendations are made for evaluation of post insulator flashover strength using the clean-fog artificial contamination test
Keywords :
flashover; insulators; pollution; power convertors; substations; HVDC converter stations; clean-fog artificial contamination test; contamination measurements; field measurements; polarity; post insulator flashover strength; stress; voltage magnitude; Contamination; Data analysis; Flashover; HVDC transmission; Insulation; Insulator testing; Pollution measurement; Senior members; Stress; Surface contamination; Switches; Testing; Voltage;
Journal_Title :
Power Delivery, IEEE Transactions on