DocumentCode :
1053087
Title :
Sensitivity Analysis of the Optimum Performance of Conventional Load-Frequency Control
Author :
Willems, J.L.
Author_Institution :
University of Gent
Issue :
5
fYear :
1974
Firstpage :
1287
Lastpage :
1291
Abstract :
This paper deals with the determination of optimum parameter values of conventional load-frequency regulation of interconnected power systems. It is shown that the control performance is rather insensitive to changes of the parameters in the vicinity of their optimum values. On the other hand the optimum value of the bias parameter depends strongly on the weighting factors used in the penalty function, as well as on the numerical data of the power system model. The importance of such sensitivity considerations is discussed in connection with the recommendation made by Elgerd and Fosha to have a bias setting which is lower than the natural frequency characteristic of the controlled area.
Keywords :
Control systems; Error correction; Frequency; Mathematical model; Power system control; Power system dynamics; Power system interconnection; Power system modeling; Power systems; Sensitivity analysis;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1974.293852
Filename :
4075491
Link To Document :
بازگشت