Title :
Sensitivity Analysis of the Optimum Performance of Conventional Load-Frequency Control
Author_Institution :
University of Gent
Abstract :
This paper deals with the determination of optimum parameter values of conventional load-frequency regulation of interconnected power systems. It is shown that the control performance is rather insensitive to changes of the parameters in the vicinity of their optimum values. On the other hand the optimum value of the bias parameter depends strongly on the weighting factors used in the penalty function, as well as on the numerical data of the power system model. The importance of such sensitivity considerations is discussed in connection with the recommendation made by Elgerd and Fosha to have a bias setting which is lower than the natural frequency characteristic of the controlled area.
Keywords :
Control systems; Error correction; Frequency; Mathematical model; Power system control; Power system dynamics; Power system interconnection; Power system modeling; Power systems; Sensitivity analysis;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1974.293852