DocumentCode
1055136
Title
Comparison of calibration systems for magnetic field measurement equipment
Author
Frix, William M. ; Karady, George G. ; Venetz, Brian A.
Author_Institution
Arizona State Univ., Tempe, AZ, USA
Volume
9
Issue
1
fYear
1994
fDate
1/1/1994 12:00:00 AM
Firstpage
100
Lastpage
108
Abstract
The current ANSI/IEEE standard specifies two possible methods for magnetic meter calibration: a single square loop or a round Helmholtz coil. However it: (a) does not specify the size of the coil; and (b) does not provide a comparison of the field uniformities between the two suggested systems. In this paper, the z-directed magnetic field equations for four calibration system designs, the single round loop, the round Helmholtz coil, the single square loop, and the square Helmholtz coil are derived and presented
Keywords
calibration; magnetic field measurement; magnetometers; measurement standards; measurement systems; measurement theory; ANSI/IEEE standard; calibration systems; field uniformities; magnetic field measurement; magnetic meter; measurement equipment; round Helmholtz coil; single round loop; single square loop; square Helmholtz coil; z-directed magnetic field equations; ANSI standards; Calibration; Coils; Equations; IEEE members; Magnetic field measurement; Magnetic fields; Measurement standards; Rivers; Shape;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.277684
Filename
277684
Link To Document