DocumentCode :
1075571
Title :
Breakdown Phenomena in SF6 and Very Inhomogeneous Large Rod-Plane Gaps under 50 HZ-AC and Positive Impulse Voltages
Author :
Zwicky, M.
Author_Institution :
Swiss Federal Institute Of Technology High-Voltage Engineering Group Zurich Switzerland
Issue :
3
fYear :
1987
fDate :
6/1/1987 12:00:00 AM
Firstpage :
317
Lastpage :
324
Abstract :
Results of breakdown measurements in SF6 are presented using very inhomogeneous large rod-plane gaps, 50 Hz ac and impulse voltage at pressures from 0.05 to 0.6 MPa. It is shown that for both voltage forms breakdown occurs over the whole pressure range due to a transition of the discharge mechanism from streamer to leader development. It was possi ble to determine the leader inception voltage. The minimal possible breakdown voltage of such large inhomogeneous gaps is practically independent of pressure over a range from 0.3 to 0.6 MPa and can be described by a simple empirical re lationship as a function of the gap width.
Keywords :
Breakdown voltage; Corona; Electric breakdown; Electrodes; Gas insulation; Nonuniform electric fields; Partial discharges; Performance evaluation; Sulfur hexafluoride; Testing;
fLanguage :
English
Journal_Title :
Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9367
Type :
jour
DOI :
10.1109/TEI.1987.298997
Filename :
4081415
Link To Document :
بازگشت