• DocumentCode
    1077451
  • Title

    Two-Stage Uninterruptible Power Supply With High Power Factor

  • Author

    Vázquez, Nimrod ; Villegas-Saucillo, JesÙs ; Hernández, Claudia ; Rodríguez, Elias ; Arau, Jaime

  • Author_Institution
    Electron. Eng. Dept., Inst. Tecnol. de Celaya, Celaya
  • Volume
    55
  • Issue
    8
  • fYear
    2008
  • Firstpage
    2954
  • Lastpage
    2962
  • Abstract
    An uninterruptible power supply (UPS) with high power factor and two conversion stages is suggested. The double-conversion configuration has three stages, but normally, only two stages are operating at the same time. The first stage of the proposed scheme integrates the power-factor-correction stage and the battery charger of the double-conversion configuration, obtaining a two-stage UPS. The second stage is based on the theory of inverter with boosting capabilities. The battery set has not only been completely isolated, but it has also been charged with a small change at the controller set point; these particular characteristics facilitate the system maintenance and simplify its operation. Additionally, the battery-set voltage is low, reducing the weight and size. The converter operation, analysis, design, and experimental results are shown. The proposed UPS approach is practical in low-power applications (les 500 W).
  • Keywords
    battery chargers; invertors; power factor correction; uninterruptible power supplies; UPS approach; battery charger; controller set point; double-conversion configuration; high power factor; inverter theory; low battery-set voltage; power-factor-correction stage; system maintenance; two-stage uninterruptible power supply; Battery chargers; boost inverters; high power factor; uninterruptible power systems;
  • fLanguage
    English
  • Journal_Title
    Industrial Electronics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0278-0046
  • Type

    jour

  • DOI
    10.1109/TIE.2008.918475
  • Filename
    4455606