DocumentCode
1077451
Title
Two-Stage Uninterruptible Power Supply With High Power Factor
Author
Vázquez, Nimrod ; Villegas-Saucillo, JesÙs ; Hernández, Claudia ; Rodríguez, Elias ; Arau, Jaime
Author_Institution
Electron. Eng. Dept., Inst. Tecnol. de Celaya, Celaya
Volume
55
Issue
8
fYear
2008
Firstpage
2954
Lastpage
2962
Abstract
An uninterruptible power supply (UPS) with high power factor and two conversion stages is suggested. The double-conversion configuration has three stages, but normally, only two stages are operating at the same time. The first stage of the proposed scheme integrates the power-factor-correction stage and the battery charger of the double-conversion configuration, obtaining a two-stage UPS. The second stage is based on the theory of inverter with boosting capabilities. The battery set has not only been completely isolated, but it has also been charged with a small change at the controller set point; these particular characteristics facilitate the system maintenance and simplify its operation. Additionally, the battery-set voltage is low, reducing the weight and size. The converter operation, analysis, design, and experimental results are shown. The proposed UPS approach is practical in low-power applications (les 500 W).
Keywords
battery chargers; invertors; power factor correction; uninterruptible power supplies; UPS approach; battery charger; controller set point; double-conversion configuration; high power factor; inverter theory; low battery-set voltage; power-factor-correction stage; system maintenance; two-stage uninterruptible power supply; Battery chargers; boost inverters; high power factor; uninterruptible power systems;
fLanguage
English
Journal_Title
Industrial Electronics, IEEE Transactions on
Publisher
ieee
ISSN
0278-0046
Type
jour
DOI
10.1109/TIE.2008.918475
Filename
4455606
Link To Document