    Integration of MHD Plants into Electric Utility Systems

  • Author

    Jackson, William D. ; Feero, William E. ; Seikel, George R. ; Gish, William B.

  • Author_Institution
    HMJ Corporation, P.O. Box 15128, Chevy Chase, MD 20815
  • Issue
    3
  • fYear
    1986
  • Firstpage
    26
  • Lastpage
    33
  • Abstract
    This paper considers the behavior of an MHD/steam-comined cylce plant under the dynamic operating conditions prescribed by the transient stability regime (50 msc to 10 sec after a disturbance on a power system). Using a three-phase fault to ground to test the model developed, it is shown that: (1) in this regime, the MHD generator acts as a current source to provide damping and consequent increased network stability; (2) the low energy storage capability of the MED generator reduces fault currents and plant surges relative to those of a similarly rated conventional plant; and (3) load tripping introduces special requirements which are discussed in the paper.
  • Keywords
    Damping; Energy storage; Magnetohydrodynamic power generation; Power industry; Power system dynamics; Power system faults; Power system modeling; Power system stability; Power system transients; Testing;