DocumentCode :
1116759
Title :
Behavior of post arc gas after arc interruption on UHV (1000 kV class) transmission lines
Author :
Goda, Yutaka ; Matsuda, Shoji ; Inaba, Tsuginori ; Ozaki, Yuzo
Author_Institution :
Central Res. Inst. of Electr. Power Ind., Kanagawa, Japan
Volume :
9
Issue :
2
fYear :
1994
fDate :
4/1/1994 12:00:00 AM
Firstpage :
887
Lastpage :
893
Abstract :
It is very important to know the insulation recovery time after arc interruption for selecting the adequate reclosing dead time of rapid auto-reclosing on transmission lines. In order to study insulation recovery characteristics after arc interruption on UHV (1000 kV class) transmission lines, many tests were carried out. Full size insulator assemblies were used for measurements of insulation recovery characteristics after arc interruption, and the behavior of post arc gases, which strongly influence the insulation recovery characteristics, was investigated. In this paper the authors describe the behavior of post arc gases after arc interruption of UHV transmission lines
Keywords :
circuit-breaking arcs; high-voltage engineering; insulation testing; power transmission lines; 1000 kV; UHV transmission lines; arc interruption; buoyancy height; insulator assemblies; post arc gas behaviour; rapid auto-reclosing; reclosing dead time; Assembly; Gas insulation; Gases; Insulation testing; Insulator testing; Poles and towers; Power transmission lines; Size measurement; Transmission line measurements; Transmission lines;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.296271
Filename :
296271
Link To Document :
بازگشت