• DocumentCode
    112307
  • Title

    Design of Post Metal Shields Through Electric Field Distribution Analysis for a 154-kV SFCL

  • Author

    Jaeun Yoo ; Woo-Ju Shin ; Young-Hee Han ; Bang Wook Lee ; Hey-Rim Kim ; Seong Eun Yang ; Heesun Kim ; Seung-Duck Yu ; Kijun Park

  • Author_Institution
    Korea Electr. Power Res. Inst., Daejeon, South Korea
  • Volume
    25
  • Issue
    3
  • fYear
    2015
  • fDate
    Jun-15
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Korea Electric Power Corporation has developed a 154-kV superconducting fault current limiter (SFCL). This report is a part of the design process of the SFCL, particularly for fixation of posts supporting the superconducting element on the cryostat wall side. For supporting the superconducting element, the use of a post insulator is inevitable; however, the post insulator and cryostat with liquid nitrogen (L-N2) during operation of the SFCL form three junction points where electric field is intensified. In this study, we aim to design the metal shield in order to relax the electric field intensity at triple points (TPs) through numerical analysis of electric field distribution. For the electric field distribution analysis, a commercial software based on the finite-element method was employed. Each design for the metal shield was checked whether it makes the electric field intensity at the TP sufficiently lower than dielectric strength in L-N2 for 750-kV input and whether there is any electrically weak point on the metal. The designs of the metal shields were improved through four critical steps where thermal contraction, manufacture tolerance, and insulation distance in L-N2 were considered. It was experimentally verified that there was no electric breakdown in L-N2 between the metal shield and the fiber-reinforced plastic post insulator for the lightning impulse test and the ac breakdown voltage test according to the IEC 60137 standard.
  • Keywords
    IEC standards; cryostats; electric fields; electric strength; fibre reinforced plastics; finite element analysis; insulators; lightning; magnetic shielding; superconducting fault current limiters; IEC 60137 standard; Korea Electric Power Corporation; SFCL; ac breakdown voltage test; cryostat wall side; dielectric strength; electric field distribution analysis; electric field intensity; fiber-reinforced plastic; finite element method; insulation distance; lightning impulse test; liquid nitrogen; manufacture tolerance; numerical analysis; post insulator; post metal shields; superconducting element; superconducting fault current limiter; thermal contraction; triple points; voltage 154 kV; voltage 750 kV; Corona; Electric fields; Finite element analysis; Insulators; Lightning; Metals; Finite element methods; finite element methods; relaxation of electric field; superconducting fault current limiters; triple points;
  • fLanguage
    English
  • Journal_Title
    Applied Superconductivity, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1051-8223
  • Type

    jour

  • DOI
    10.1109/TASC.2014.2387117
  • Filename
    7000569