DocumentCode
1127318
Title
Redundancy and Observability Analysis of Conventional and PMU Measurements
Author
London, J. B A, Jr. ; Piereti, S.A.R. ; Benedito, R.A.S. ; Bretas, N.G.
Author_Institution
Dept. of Electr. Eng., Univ. of Sao Paulo, Sao Carlos, Brazil
Volume
24
Issue
3
fYear
2009
Firstpage
1629
Lastpage
1630
Abstract
This letter shows that the H Delta matrix can be used for redundancy and observability analysis of metering systems composed of PMU measurements and conventional measurements (power and voltage magnitude measurements). The H Delta matrix is obtained via triangular factorization of the Jacobian matrix. Observability analysis and restoration is carried out during the triangular factorization of the Jacobian matrix, and the redundancy analysis is made exploring the H Delta matrix structure. As a consequence, the H Delta matrix can be used for metering system planning considering conventional and PMU measurements. These features of the H Delta matrix will be outlined and illustrated by numerical examples.
Keywords
Jacobian matrices; observability; phase measurement; power measurement; power meters; power system measurement; Jacobian matrix; PMU measurements; metering system planning; observability analysis; power measurements; redundancy analysis; triangular factorization; voltage magnitude measurements; Network observability; phasor measurement units; redundancy analysis; state estimation;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/TPWRS.2009.2021195
Filename
5159362