DocumentCode
1127679
Title
Operation of a Medium-Voltage Drive Under Faulty Conditions
Author
Rodríguez, José ; Hammond, Peter W. ; Pontt, Jorge ; Musalem, Rodrigo ; Lezana, Pablo ; Escobar, María José
Author_Institution
Electron. Eng. Dept., Univ. Tecnica Federico Santa Maria, Valparaiso, Chile
Volume
52
Issue
4
fYear
2005
Firstpage
1080
Lastpage
1085
Abstract
This paper presents a method for operating cascaded multilevel inverters when one or more power cells are damaged. The method is based on the use of additional switches in the power circuit to bypass the faulty cell. To control the cells, the angle of phase shifting in the carrier signals is modified according to the number of operating cells, to minimize the load voltage distortion, when the inverter operates in failure mode. The reference signals of the pulsewidth-modulation modulators are also modified to increase the output voltage. Simulation and experimental results show the effectiveness of this method, which significantly increases the reliability of the drive.
Keywords
PWM invertors; fault tolerance; induction motor drives; pulsed power switches; carrier signals; cascaded multilevel inverters; fault tolerance; faulty cell; load voltage distortion; medium-voltage drive; phase shifting; power cells; pulse width modulation; Circuit faults; Circuit topology; Medium voltage; Phase distortion; Pulse modulation; Pulse width modulation inverters; Switches; Switching circuits; Switching frequency; Voltage control; Fault tolerance; multilevel inverters; power electronics;
fLanguage
English
Journal_Title
Industrial Electronics, IEEE Transactions on
Publisher
ieee
ISSN
0278-0046
Type
jour
DOI
10.1109/TIE.2005.851645
Filename
1490698
Link To Document