DocumentCode
1142007
Title
The establishment of 10-500/√3kV power frequency voltage ratio standard apparatus and study of the calibration method
Author
Gao, Guanggan ; Zhao, Baowang
Author_Institution
Nat. High Voltage Meterage Station, Wuhan, China
Volume
43
Issue
4
fYear
1994
fDate
8/1/1994 12:00:00 AM
Firstpage
671
Lastpage
675
Abstract
The principle of 10-500/√3-kV power frequency voltage ratio standard apparatus and the calibration method at NHVMS, China, are presented in this paper. The substitution method which is usually used for low-voltage precise measurement was applied to the field of high-voltage measurement. A new method was developed. It is renamed “the incomplete substitution method” because the operating voltages and currents of the components of the standard apparatus are different before and after substitution. The systematic errors of the components due to the difference of operating states are measured in advance and can be corrected, so the measuring accuracy is improved greatly. The error analysis shows that the total uncertainties of the standard apparatus are better than ±10 ppm in magnitude and ±10 μrad in phase angle (the confidence factor is 3). The comparison result between China and Canada is satisfactory
Keywords
calibration; high-voltage techniques; measurement errors; measurement standards; voltage measurement; 10 kV; Canada; China; NHVMS; calibration; error analysis; high-voltage measurement; phase angle; power frequency voltage ratio standard; substitution method; systematic errors; total uncertainties; Bandwidth; Calibration; Equations; Frequency measurement; Laser noise; Laser stability; Oscillators; Semiconductor device noise; Semiconductor lasers; Voltage;
fLanguage
English
Journal_Title
Instrumentation and Measurement, IEEE Transactions on
Publisher
ieee
ISSN
0018-9456
Type
jour
DOI
10.1109/19.310188
Filename
310188
Link To Document