DocumentCode :
1150644
Title :
AC filter arrester application
Author :
Harder, John E.
Volume :
11
Issue :
3
fYear :
1996
fDate :
7/1/1996 12:00:00 AM
Firstpage :
1355
Lastpage :
1360
Abstract :
Arresters are being used in increasing numbers to provide surge protection inside of harmonic filters. The continuous voltage across these arresters is frequently a mixture of significant magnitudes of various harmonic voltages. Temporary overvoltages may result from system overvoltages or filter overloading. This investigation considers both the continuous arrester heating caused by a mixture of harmonic voltages and the effect of temporary overvoltages in order to provide guidelines for the appropriate selection of an arrester voltage rating for this type of application
Keywords :
arresters; overvoltage; power filters; power system harmonics; AC filter arrester; arrester voltage rating; continuous voltage; filter overloading; harmonic filters; harmonic voltages; losses estimation; surge protection; temporary overvoltages; Arresters; Capacitors; Dielectric losses; Frequency; Heating; Power harmonic filters; Power system harmonics; Surge protection; Surges; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.517491
Filename :
517491
Link To Document :