Testing Magnetic Air Circuit Breakers for 5-Cycle Performance
Author
Wood, J.D. ; Carter, W.A.
Volume
77
Issue
3
fYear
1958
fDate
4/1/1958 12:00:00 AM
Firstpage
1560
Lastpage
1562
Abstract
Magnetic air circuit breakers are now rated 8 cycles even though they inherently demonstrate 5-cycle performance. It is therefore the responsibility of the manufacturer to test the circuit breakers so that the duty imposed by the system does not result in misapplications. To assure proper application as 5-cycle breakers the tests should show that: 1. The interrupting time does not exceed 5 cycles. 2. The rated interrupting current shall be symmetrical amperes. 3. An asymmetrical current, whose total rms value is 10% greater than the rated interrupting current, be interrupted. 4. All interrupting tests be made with a recovery voltage equal to the system voltage.
Keywords
Associate members; Circuit breakers; Circuit faults; Circuit testing; Delay; Magnetic circuits; Manufacturing; Relays; System testing; Voltage;