• DocumentCode
    1162521
  • Title

    Effect of Time Shift Between the two Voltage Components on Phase-to-Phase Insulation Strength

  • Author

    Kosztaluk, Romuald ; Lanoie, Robert ; Malewski, Ryszard ; Menemenlis, Christos ; Nguyen, Duc-Hai

  • Author_Institution
    Institut Energetyki
  • Issue
    7
  • fYear
    1981
  • fDate
    7/1/1981 12:00:00 AM
  • Firstpage
    3379
  • Lastpage
    3386
  • Abstract
    A study on the phase-to-phase strength of a conductor-conductor configuration was performed in IREQ´s High-Voltage Laboratory in an attempt to determine the influence of a time shift, ATcr, between the positive and negative voltage components on the 50% breakdown voltage. The gap tested was formed by two parallel conductors 6.7 m apart. Positive impulses of up to 2.3 MV, negative impulses of up to 3.2 MV and time shifts of up to 7.5 ms were used. The breakdown voltage, space charge and electric field on the electrode surface were monitored during the tests and photographs were taken with an image-converter camera.
  • Keywords
    Conductors; Costs; Dielectrics and electrical insulation; Laboratories; Reliability; Substations; Surges; Testing; Time measurement; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1981.316680
  • Filename
    4111017