• DocumentCode
    1162754
  • Title

    Development of a Reduced Wall 138kV HPOF Pipe Type Cable and Joints for RE-Conductoring of Existing 69kV Lines on the Florida Power & Light Company System

  • Author

    Prime, J.B., Jr. ; Valdes, J.G. ; Silver, D.A. ; Seman, G.W. ; Dima, A.F. ; Buckweitz, M.D.

  • Author_Institution
    Florida Power & Light Company
  • Issue
    7
  • fYear
    1981
  • fDate
    7/1/1981 12:00:00 AM
  • Firstpage
    3617
  • Lastpage
    3625
  • Abstract
    A 138kV pipe type cable with 348 mils (8.8mm) of paper insulation and two types of joints have been developed for re-conductoring existing 69kV HPOF pipe type cable circuits installed in 6-5/8 inch (168mm) pipes on the Florida Power & Light Company system. A cost saving of 60 percent or $11.7 million will be realized in the re-conductoring of 15.9 miles (25.6km) of circuit compared to installation of new 138kV cables in 8-5/8 inch (219mm) pipe. Laboratory test data on cable as manufactured and on cable returned after one year in-service operation at the Florida Power & Light test site validate the adequacy of the optimized design.
  • Keywords
    Cable insulation; Circuit testing; Communication cables; Conductors; Costs; Design optimization; Dielectrics and electrical insulation; Oil filled cables; Oil insulation; Reliability;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1981.316655
  • Filename
    4111043