• DocumentCode
    1162966
  • Title

    SLF Innterruption by a Gas Circuit Breaker Without Puffer Action

  • Author

    Ushio, T. ; Tominaga, S. ; Kuwahara, H. ; Miyamoto, T. ; Ueda, Y. ; Sasao, H.

  • Author_Institution
    Mitsubishi Electric Corporation
  • Issue
    8
  • fYear
    1981
  • Firstpage
    3801
  • Lastpage
    3810
  • Abstract
    A full size model gas circuit breaker without puffer has been built and tested based on a new arc quenching principle of self-flow generation. The breaker generates the flow around current zero due to the pressure rise in the cylinder by positive utilization of nozzle clogging phenomenon. The test was carried out on BTF and SLF conditions prescribed in IEC standards. The breaker successfully interrupted 40 kA for BTF and SLF respectively at 84 kV. Based on the test results and the theoretical analysis of the self-flow generating behavior, it is remarked that the new arc quenching principle is more effective to get higher fault clearing capability compared with the puffer principle.
  • Keywords
    Automatic testing; Circuit breakers; Circuit faults; Circuit testing; Fluid flow; Gas lasers; Laser modes; Laser theory; Optical interferometry; Sulfur hexafluoride;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1981.317023
  • Filename
    4111070