• DocumentCode
    1167072
  • Title

    Evolving Fault Performance of Vacuum Switchgear on an 11kV Distribution System

  • Author

    Faragalla, Fayek Farid ; Radwan, Galal ; Monium Ragab, Abd El ; Titus, C.H. ; Ros, W.J.

  • Author_Institution
    Egyptian Electricity Authority
  • Issue
    7
  • fYear
    1982
  • fDate
    7/1/1982 12:00:00 AM
  • Firstpage
    2019
  • Lastpage
    2023
  • Abstract
    The evolving fault, a fault condition in which a fault rapidly changes in physical nature immediately after its initiation, has long been known to exist but has rarely been examined on a power distribution system. This paper describes a series of tests which were performed on the Egyptian Electricity Authority´s 11kV distribution system in Cairo, and which included simulations of the evolving fault. The paper also describes the capability of the vacuum interrupter to successfully interrupt the evolving fault, and some very unusual, unanticipated, fault current levels.
  • Keywords
    Circuit breakers; Circuit faults; Circuit testing; Fault currents; Performance evaluation; Power cables; Substations; Switchgear; System testing; Vacuum systems;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1982.317450
  • Filename
    4111554