DocumentCode :
1167099
Title :
Operation of a Power Line Carrier System during Sustained Line Faults
Author :
Jones, D.E.
Volume :
79
Issue :
3
fYear :
1960
fDate :
4/1/1960 12:00:00 AM
Firstpage :
556
Lastpage :
559
Abstract :
Tests to assess the reliability of a power line carrier system during sustained line faults have shown that a carrier operating range of about 60 db (decibels), in addition to that required for normal line attenuation, should permit reliable operation through faults. The use of line-to-line coupling provides no more than 8 db advantage over line-to-ground coupling.
Keywords :
Attenuation measurement; Circuit faults; Circuit noise; Coupling circuits; Power system faults; Power system reliability; Power system transients; Protective relaying; Supervisory control; Testing;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers