DocumentCode
1167591
Title
A Method of Calculating the Voltage Distribution of Cascade-Connected Testing Transrormers
Author
Schaffer, H.E.
Volume
79
Issue
3
fYear
1960
fDate
4/1/1960 12:00:00 AM
Firstpage
771
Lastpage
776
Abstract
For design purposes cascadedtesting transformer circuits can be reduced to equivalent inductance and capacitance networks by properly combining the circuit elements. After establishing the circuit conditions, the initial surge voltage to ground at any point in the circuit and at any time can be calculated, thereby fixing an insulation design level for all units of the cascade set. The inductance and capacitance elements of the cascaded windings involved are identified and are reduced to an equivalent twoor three-mesh network, and the method for calculating the surge distribution across each unit is developed. Formulas, curves, and diagrams for the various steps are included and oscillograms of test waves are shown to establish the accuracy and validity of the method.
Keywords
Capacitance; Circuit testing; Inductance; Power cables; Power transformer insulation; Power transformers; Soil; Surges; Temperature; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
Publisher
ieee
ISSN
0097-2460
Type
jour
DOI
10.1109/AIEEPAS.1960.4500857
Filename
4500857