DocumentCode :
1177986
Title :
Influence of Representation Model and Voltage Harmonics on Metal Oxide Surge Arrester Diagnostics
Author :
Zhu, Hengliang ; Raghuveer, M. R.
Author_Institution :
University of Manitoba, Winnipeg, Canada
Volume :
21
Issue :
8
fYear :
2001
Firstpage :
62
Lastpage :
62
Abstract :
Test results have been presented to demonstrate the hysteretic character of the volt-ampere relation of a metal oxide surge arrester (MOSA). Using a compensation technique described in the paper, it is shown that the use of single valued average volt-ampere characteristics does not introduce large errors in simulation studies. Results from computer simulations are presented to demonstrate the considerable influence of harmonics in the applied voltage on the magnitude of diagnostic indicators.
Keywords :
Arresters; Circuit breakers; Equations; HVDC transmission; Load flow control; Sociotechnical systems; Sulfur hexafluoride; Surges; Switches; Voltage control; Metal oxide surge arrester; diagnostic indicators; hysteretic volt-ampere relation; voltage harmonics;
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.2001.4311569
Filename :
4311569