DocumentCode :
1182397
Title :
Dielectric Phase in an SF6 Model Breaker
Author :
Schoetzau, H.J. ; Meili, H.P. ; Fischer, E. ; Sturzenegger, CH. ; Graf, H.P.
Author_Institution :
Physics Laboratory
Issue :
7
fYear :
1985
fDate :
7/1/1985 12:00:00 AM
Firstpage :
1897
Lastpage :
1902
Abstract :
In SF6 circuit breakers the arcing region is stressed by the applied recovery voltage after current interruption. A channel of hot gas of reduced density can be observed at the place where the arc has burnt. The spatial and temporal development of this hot gas channel and its temperature have been investigated under various experimental conditions using a model breaker. The results are compared to theoretical calculations describing the temperature decay in the upstream region of a double flow arrangement during the dielectric phase.
Keywords :
Circuit breakers; Dielectrics; Fluid flow; Laboratories; Optical interferometry; Physics; Sulfur hexafluoride; Temperature; Testing; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1985.319182
Filename :
4113317
Link To Document :
بازگشت