DocumentCode :
1186696
Title :
Numerical Electromagnetic Field Analysis of Arc-Horn Voltages during a Back-Flashover on a 500 KV Twin-Circuit Line
Author :
Mozumi, T. ; Baba, Yuya ; Ishii, M. ; Nagaoka, Naoto ; Ametani, Akihiro
Author_Institution :
Hokuriku Electric Power Company; Doshisha University
Volume :
22
Issue :
8
fYear :
2002
Firstpage :
72
Lastpage :
72
Abstract :
Arc-horn voltages of a simulated 500 kV twin-circuit line in the case of one-phase back-flashover due to lightning to a tower top are analyzed by the thin-wire time-domain analysis (TWTDA) code. Prior to this analysis, a recently proposed flashover model is incorporated into TWTDA. It becomes clear that the arc-horn voltages of the other two phases show a quite similar time-varying characteristic alter one phase back-flashover. An EMTP simulation is also carried out. The archom voltages computed by EMTP agree well with those computed by TWTDA before the back-flashover on one phase. On the other hand, during about 1 ??s after the one-phase back-flashover, the arc-horn voltages of the other two phases computed by EMTP deviate much from those computed by TWTDA. Particularly in the case of the middle-or the lower-phase back-flashover, the deviation is noticeable. The reason for this discrepancy is discussed.
Keywords :
Analytical models; Computational modeling; EMTP; Electromagnetic analysis; Electromagnetic fields; Flashover; Lightning; Poles and towers; Time domain analysis; Voltage; Back-flashover; EMTP; lightning surge; numerical electromagnetic field analysis;
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.2002.4312531
Filename :
4312531
Link To Document :
بازگشت