DocumentCode :
1186822
Title :
Influence of Short-Circuit Currents on HV and EHV Strain Bus Design
Author :
Awad, M.B. ; Huestis, H.W.
Author_Institution :
Ontario Hydro Transmission Systems Division
Issue :
2
fYear :
1980
fDate :
3/1/1980 12:00:00 AM
Firstpage :
480
Lastpage :
487
Abstract :
Methods are presented to design strain bus for short-circuit currents up to 100 kA rms for new 230 and 500 kV substations and to uprate existing substations. Mechanical, electrical and arc-thermal effects of short-circuit currents on strain-bus systems as they are affected by various design parameters are discussed. These parameters include span length, number and lengths of subspons, bundle-conductor spacing, short-circuit current magnitude and duration. New techniques to reduce short-circuit effects on strain-bus systems for minimum service disruption and cost include the use of polymeric insulated phase-phase spacers, small bundle-conductor spacing, insulation coordination and bay-by-bay analysis of forces on the supporting structures.
Keywords :
Capacitive sensors; Conductors; Costs; Fault currents; Plastic insulation; Polymers; Senior members; Steel; Substations; Testing;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1980.319683
Filename :
4113826
Link To Document :
بازگشت