DocumentCode :
1191217
Title :
Protection Zone for Buildings Against Lighning Strokes Using Transmission Line Protection Practice
Author :
Lee, Ralph H.
Author_Institution :
Lee Electrical Engineering, Inc., Wilmington, DE 19807.
Issue :
6
fYear :
1978
Firstpage :
465
Lastpage :
469
Abstract :
The nature of the zone of protection of structures from an elevated rod or wire, inadequately defined in the past, can be determined with high reliability using data developed by E.R.Whitehead of the Illinois Institute of Technology under contract from the Edison Electric Institute for the protection of high-voltage electric transmission lines. The vertical boundary of this zone of protection is not linear, as has been believed in the past, but is a circular arc, tangent to the ground, of 150-ft radius for 99.5 percent protection and 125-ft radius for 99.9 percent protection.
Keywords :
Buildings; Contracts; Engine cylinders; Industrial power systems; Lightning; Power system modeling; Power system protection; Shape; Transmission line theory; Wire;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/TIA.1978.4503576
Filename :
4503576
Link To Document :
بازگشت