DocumentCode
1200707
Title
A field experiment on power line stabilization by a SMES system
Author
Irie, F. ; Takeo, M. ; Sato, S. ; Katahira, O. ; Fukui, F. ; Okada, H. ; Ezaki, T. ; Ogawa, K. ; Koba, H. ; Takamatsu, M. ; Shimojo, T.
Author_Institution
Kinki Univ., Iizuka, Japan
Volume
28
Issue
1
fYear
1992
fDate
1/1/1992 12:00:00 AM
Firstpage
426
Lastpage
429
Abstract
Field experiments on stabilization of a hydro power plant by a SMES (superconducting magnetic energy storage) system are reported, where a generator having a rating of 60 kW at 3.3 kV is connected to a 6.6 kV power distribution line. The SMES system is composed of two 30 kVA GTO (gate turn off) converters and a superconducting magnet system with an energy of 30 kJ at 100 A. Experiments on stabilization for the generator fluctuation caused by a sudden insertion of inductors in the line were successfully performed for some control modes. The value of the SMES system to compensate for a short-period voltage dip is also confirmed
Keywords
hydroelectric power stations; power cables; stability; superconducting magnet energy storage; 3.3 kV; 30 kJ; 30 kVA; 6.6 kV; 60 kW; GTO converters; SMES system; control modes; field experiment; generator; hydro power plant; power line stabilization; short-period voltage dip; superconducting magnet system; superconducting magnetic energy storage; Converters; Electric variables control; Grounding; Impedance; Inductors; Power distribution lines; Power generation; Power system transients; Samarium; Voltage fluctuations;
fLanguage
English
Journal_Title
Magnetics, IEEE Transactions on
Publisher
ieee
ISSN
0018-9464
Type
jour
DOI
10.1109/20.119902
Filename
119902
Link To Document