• DocumentCode
    1200707
  • Title

    A field experiment on power line stabilization by a SMES system

  • Author

    Irie, F. ; Takeo, M. ; Sato, S. ; Katahira, O. ; Fukui, F. ; Okada, H. ; Ezaki, T. ; Ogawa, K. ; Koba, H. ; Takamatsu, M. ; Shimojo, T.

  • Author_Institution
    Kinki Univ., Iizuka, Japan
  • Volume
    28
  • Issue
    1
  • fYear
    1992
  • fDate
    1/1/1992 12:00:00 AM
  • Firstpage
    426
  • Lastpage
    429
  • Abstract
    Field experiments on stabilization of a hydro power plant by a SMES (superconducting magnetic energy storage) system are reported, where a generator having a rating of 60 kW at 3.3 kV is connected to a 6.6 kV power distribution line. The SMES system is composed of two 30 kVA GTO (gate turn off) converters and a superconducting magnet system with an energy of 30 kJ at 100 A. Experiments on stabilization for the generator fluctuation caused by a sudden insertion of inductors in the line were successfully performed for some control modes. The value of the SMES system to compensate for a short-period voltage dip is also confirmed
  • Keywords
    hydroelectric power stations; power cables; stability; superconducting magnet energy storage; 3.3 kV; 30 kJ; 30 kVA; 6.6 kV; 60 kW; GTO converters; SMES system; control modes; field experiment; generator; hydro power plant; power line stabilization; short-period voltage dip; superconducting magnet system; superconducting magnetic energy storage; Converters; Electric variables control; Grounding; Impedance; Inductors; Power distribution lines; Power generation; Power system transients; Samarium; Voltage fluctuations;
  • fLanguage
    English
  • Journal_Title
    Magnetics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9464
  • Type

    jour

  • DOI
    10.1109/20.119902
  • Filename
    119902