DocumentCode :
1212775
Title :
Risk of burn-through-a quantitative assessment of the capability of gas-insulated equipment to withstand internal arcs
Author :
Trinh, N. Giao
Author_Institution :
Inst. de Recherche d´´Hydro-Quebec, Varennes, Que., Canada
Volume :
7
Issue :
1
fYear :
1992
fDate :
1/1/1992 12:00:00 AM
Firstpage :
225
Lastpage :
236
Abstract :
The author introduces the notion of the risk of burn-through, borrowed from the risk of failure widely used in the statistical approach to insulation coordination, to evaluate the capability of gas-insulated equipment and substations (GIS) to withstand burn-through due to internal arcs. A sensitivity analysis performed to identify the main parameters affecting the risk of burn-through showed that the risk increases with the mean fault current. Both the fault-clearing characteristics of the switching apparatus and the GIS design, namely the envelope thickness and the GIS section length between two consecutive insulators, were found to have a significant influence on the risk of burn-through. To keep the risk of burn-through reasonably low, appropriate coordination must be made among the fault-clearing characteristics of the switching apparatus, the GIS design, and the distribution of the local fault currents
Keywords :
arcs (electric); fault currents; gaseous insulation; substations; GIS; burn-through; fault-clearing characteristics; gas-insulated equipment; gas-insulated substations; insulators; internal arcs; local fault currents; sensitivity analysis; Fault currents; Fault diagnosis; Gas insulated transmission lines; Gas insulation; Geographic Information Systems; Power overhead lines; Power transmission lines; Rivers; Sensitivity analysis; Substations;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.108912
Filename :
108912
Link To Document :
بازگشت