DocumentCode :
1213055
Title :
Hotspot location and mitigation for underground power cables
Author :
Su, Q. ; Li, H.J. ; Tan, K.C.
Author_Institution :
SP PowerGrid Ltd., Singapore, Singapore
Volume :
152
Issue :
6
fYear :
2005
Firstpage :
934
Lastpage :
938
Abstract :
Cable current-carrying capacity (ampacity) is limited by hotspots. Based on distributed temperature sensing, the hotspots of a 230 kV 500 MVA underground cable circuit were located. The derating at each hotspot was calculated using a new technique, which helped to determine more accurately the thermal environment parameters at the hotspot. Case studies are presented to show the successful restoration of full cable rating after the hotspots were mitigated.
Keywords :
fault location; power cable insulation; power cable testing; temperature distribution; temperature sensors; underground cables; 230 kV; 500 MVA; cable current-carrying capacity; cable rating; distributed temperature sensing; hotspot location; thermal environment parameters; underground power cables;