DocumentCode :
1217685
Title :
Equivalent circuit for high-voltage partial-core resonant transformers
Author :
Bell, S.C. ; Bodger, P.S.
Author_Institution :
Electr. & Comput. Eng., Canterbury Univ., Christchurch
Volume :
2
Issue :
3
fYear :
2008
fDate :
5/1/2008 12:00:00 AM
Firstpage :
155
Lastpage :
163
Abstract :
An equivalent circuit model for the partial-core resonant transformer is presented. A model which omits core losses is first introduced and is verified on a sample air-core resonant transformer. Partial-cores are then introduced into the transformer and the resonant characteristics are re-measured. The model is modified to account for the core losses and then verified against the measured data. Comparisons and transformations between the model and the Steinmetz ´exact´ transformer equivalent circuit are given. A procedure for measuring the equivalent circuit inductances is described and then used to investigate the inductance variation with core displacement characteristics of the sample transformer in both axial-offset and centre-gap arrangements. In a capacitive load test the sample transformer was linear to a significantly higher voltage when using the centre-gap arrangement.
Keywords :
equivalent circuits; inductance; transformer cores; Steinmetz transformer equivalent circuit; axial-offset arrangements; capacitive load test; centre-gap arrangements; core losses; equivalent circuit inductances; high-voltage partial-core resonant transformers;
fLanguage :
English
Journal_Title :
Electric Power Applications, IET
Publisher :
iet
ISSN :
1751-8660
Type :
jour
DOI :
10.1049/iet-epa:20070430
Filename :
4519792
Link To Document :