Distributed Generation for Mitigating Voltage Dips in Low-Voltage Distribution Grids
Author :
Renders, Bert ; De Gussemé, Koen ; Ryckaert, Wouter R. ; Stockman, Kurt ; Vandevelde, Lieven ; Bollen, Math H J
Author_Institution :
Dept. of Electr. Energy, Ghent Univ., Ghent
Volume :
23
Issue :
3
fYear :
2008
fDate :
7/1/2008 12:00:00 AM
Firstpage :
1581
Lastpage :
1588
Abstract :
The presence of synchronous and induction generators has a positive effect on the retained voltage (the lowest rms voltage during the event) during voltage dips in high voltage networks. The impact of converter-connected distributed-generation (DG) units has been reported to be negligible, as most converters operate at unity power factor, and the currents injected in the grid are limited to the nominal current of the converter. However, the impact of DG units on the distorted grid voltage is strongly dependent on the voltage level, and thus the grid impedance, of the concerned grid. This paper investigates and compares the effects of converter-based DG units, synchronous and asynchronous generators on the retained voltage during voltage dips in low voltage distribution grids.
Keywords :
asynchronous generators; distributed power generation; power grids; synchronous generators; converter-connected distributed-generation units; distorted grid voltage; distributed generation; induction generators; low-voltage distribution grids; synchronous generators; voltage dips; Distributed generation (DG); low voltage grids; mitigation; retained voltage; voltage dips;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2007.916162