• DocumentCode
    1296889
  • Title

    How the switching-surge family affects line insulation

  • Author

    Kalb, J.W.

  • Author_Institution
    The Ohio Brass Co., Barberton, Ohio
  • Volume
    82
  • Issue
    6
  • fYear
    1963
  • fDate
    6/1/1963 12:00:00 AM
  • Firstpage
    395
  • Lastpage
    403
  • Abstract
    Full-scale switching-surge flashover tests were made at an outdoor laboratory that covered a range of V-string and vertical insulator string lengths, tower sizes, and waveshapes. The response of line insulation to these surges was explored. Effects of precipitation and preceding trapped charge (bias voltage) were investigated, along with rod-to-ground and conductor-to-ground flashover. Estimated performance curves of EHV transmission line structures indicate economic justification for switching-surge limiting apparatus.