Abstract :
Cyclic loads such as eccentric pumping units cause a varying torque on the driver. Determination of the most efficient induction motor for the load is discussed. Ultrahigh-slip motors as well as NEMA (National Electric Manufacturers Association) design motors are evaluated. Comparisons of operating costs and investments are presented. The following is concluded: (1) any motor design will work on a pumping unit; (2) the motor must be carefully sized to provide minimum operating cost; (3) the lowest operating cost and the least investment come from the motors with the least slip; (4) the lower-slip motors cause an increase in peak torque on the unit; and (5) an accurate computer model with an easy-to-use program that allows what-if options is highly desirable
Keywords :
economics; electric machine CAD; induction motors; pumps; slip (asynchronous machines); CAD; NEMA; computer model; cyclic loads; design; eccentric pumping units; induction motor; investments; operating costs; peak torque; pumping unit; slip performance; ultrahigh slip motors; Chemical industry; Costs; Electric motors; Induction motors; Industry Applications Society; Laser excitation; Petroleum; Production; Shafts; Torque;
Journal_Title :
Industry Applications, IEEE Transactions on