Title :
Effect of DC bias on surface strength of processed pressboard under lightning and switching impulses
Author :
Raghuveer, M.R. ; Zhang, Ge ; David, F.
Author_Institution :
Manitoba Univ., Winnipeg, Man., Canada
fDate :
8/1/1991 12:00:00 AM
Abstract :
The surface strength of processed transformer pressboard is determined in a practical configuration under additive polarity composite DC plus switching impulse and DC plus lightning impulse voltages. Results obtained with specimens impregnated with field-aged oil are presented. With both types of composite voltage, most breakdowns occurred in the oil away from the interface. There is no significant influence of gap length on the location of the breakdown. With increasing DC bias fewer breakdowns occurred on the surface
Keywords :
electric breakdown of liquids; insulating oils; insulation testing; transformer insulation; DC bias; DC plus lightning impulse voltages; DC plus switching impulse; breakdowns; field-aged oil; gap length; processed pressboard; processed transformer pressboard; surface strength; Additives; Breakdown voltage; Electric breakdown; Helium; Lightning; Oil insulation; Petroleum; Power transformer insulation; Solids; Testing;
Journal_Title :
Electrical Insulation, IEEE Transactions on