    New setting of loss of excitation protection in P-Q plan in order to maximize the operation area of the capacity curve of the synchronous machine

  • Author

    Gazen, Yuri Neves ; Bubolz Zarnott, Alexandre ; Peres de Morais, Adriano ; Cardoso, Ghendy ; de Lima Oliveira, Aecio

  • Author_Institution
    Companhia Estadual de Energia Eletr., Brazil
  • fYear
    2014
  • fDate
    2-5 Sept. 2014
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    This paper presents a method for maximizing the operation area of the capacity curve of a synchronous machine. The technique is set in P-Q plan in order to adjust more features of minimum excitation and practical stability limits of the capacity curve. Thus, the voltage limiter can be intended to the left of the capacity curve and so the machine may have an operating gain in this region. The new setting is done primarily on the generator capacity curve, plan P-Q, and subsequently analyzed in the R-X plan.
  • Keywords
    machine protection; synchronous machines; P-Q plan; R-X plan; excitation protection loss; generator capacity curve; synchronous machine; Capacity planning; Impedance; Loading; Relays; Synchronous generators; Capacity Curve; Loss of Field Protection; Minimum Excitation Limit; Synchronous Generator;