Title :
Electrical and chemical diagnostics of transformers insulation. A. Aged transformer samples
Author :
Saha, T.K. ; Darveniza, M. ; Hill, D.J.T. ; Le, T.T.
Author_Institution :
Dept. of Electr. & Comput. Eng., Queensland Univ., Australia
fDate :
10/1/1997 12:00:00 AM
Abstract :
This paper describes the application of two relatively new diagnostic techniques for the determination of insulation condition in aged transformers. The techniques are: (a) measurements of interfacial polarization spectra by a DC method; and (b) measurements of molecular weight and its distribution by gel permeation chromatography. Several other electrical properties of the cellulose polymer were also investigated. Samples were obtained from a retired power transformer and they were analysed by the developed techniques. Six distribution transformers were also tested with the interfacial polarization spectra measurement technique, and the molecular weight of paper/pressboard samples from these transformers were also measured by the gel permeation chromatography. The variation of the results through different locations in a power transformer is discussed in this paper. The possible correlation between different measured properties was investigated and discussed in this paper
Keywords :
ageing; chromatography; dielectric polarisation; electric breakdown; insulation testing; paper; power transformer insulation; power transformer testing; aged insulation samples; cellulose polymer; diagnostic techniques; gel permeation chromatography; insulation condition; interfacial polarization spectra measurement; molecular weight; paper/pressboard samples; power transformer insulation diagnosis; Aging; Chemicals; Dielectrics and electrical insulation; Measurement techniques; Polarization; Polymers; Power transformer insulation; Power transformers; Testing; Weight measurement;
Journal_Title :
Power Delivery, IEEE Transactions on