Influence of high frequency current transformers bandwidth on charge evaluation in partial discharge measurements
Author
Rodrigo, A. ; Llovera, P. ; Fuster, V. ; Quijano, A.
Author_Institution
Inst. Tecnol. de la Energia - Redit, Univ. Politec. de Valencia, Valencia, Spain
Volume
18
Issue
5
fYear
2011
fDate
10/1/2011 12:00:00 AM
Firstpage
1798
Lastpage
1802
Abstract
High frequency current transformers (HFCT) are now widely used for partial discharges detection and measurement, specially for partial discharge location and source identification. However, many difficulties arise due to HFCT in the determination of the apparent charge in picocoulombs (pC) because of large variations according to sensors or pulses shapes. Some authors are even using milivolts (mV) as representative magnitude. As a result, measurements carried out using HFCT are not comparable in terms of apparent charge determination. In this paper, a new method of charge evaluation by means of HFCT is described solving the calibration procedure according to the sensor bandwidth and providing a criterion for sensors evaluation.
Keywords
calibration; current transformers; partial discharge measurement; sensors; HFCT; calibration procedure; charge evaluation; high frequency current transformers bandwidth; partial discharge measurements; partial discharges detection; picocoulombs; sensor bandwidth; sensors evaluation; Calibration; Charge measurement; Partial discharge measurement; Partial discharges; Pulse measurements; Sensors; Shape; Partial discharges; chargemeasurement; convolution; current transformers; high frequency; integration.; uncertainty;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
1070-9878
Type
jour
DOI
10.1109/TDEI.2011.6032852
Filename
6032852
Link To Document