• DocumentCode
    1338672
  • Title

    Influence of high frequency current transformers bandwidth on charge evaluation in partial discharge measurements

  • Author

    Rodrigo, A. ; Llovera, P. ; Fuster, V. ; Quijano, A.

  • Author_Institution
    Inst. Tecnol. de la Energia - Redit, Univ. Politec. de Valencia, Valencia, Spain
  • Volume
    18
  • Issue
    5
  • fYear
    2011
  • fDate
    10/1/2011 12:00:00 AM
  • Firstpage
    1798
  • Lastpage
    1802
  • Abstract
    High frequency current transformers (HFCT) are now widely used for partial discharges detection and measurement, specially for partial discharge location and source identification. However, many difficulties arise due to HFCT in the determination of the apparent charge in picocoulombs (pC) because of large variations according to sensors or pulses shapes. Some authors are even using milivolts (mV) as representative magnitude. As a result, measurements carried out using HFCT are not comparable in terms of apparent charge determination. In this paper, a new method of charge evaluation by means of HFCT is described solving the calibration procedure according to the sensor bandwidth and providing a criterion for sensors evaluation.
  • Keywords
    calibration; current transformers; partial discharge measurement; sensors; HFCT; calibration procedure; charge evaluation; high frequency current transformers bandwidth; partial discharge measurements; partial discharges detection; picocoulombs; sensor bandwidth; sensors evaluation; Calibration; Charge measurement; Partial discharge measurement; Partial discharges; Pulse measurements; Sensors; Shape; Partial discharges; chargemeasurement; convolution; current transformers; high frequency; integration.; uncertainty;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2011.6032852
  • Filename